Re: [AMMRL] Coolant for He Compressors

From: Alex Paterson via groups.io <alpaterson=wisc.edu_at_groups.io>
Date: Tue, 29 Jul 2025 16:45:49 +0000

Hi Luke,

Re 2, is it possible for you to split the difference and have a heat exchanger
between your building chilled and your process loop? That’s how we do i
t at NMRFAM.

Our process chilled water loop is closed and exclusively serves our equipment
(approx. 14 helium compressors). It has dedicated redundant lead-lag circulation
pumps. Physical Plant does periodic maintenance on the pumps and the loop itself.

The process chilled water loop rejects heat to the campus chilled water system
via a pair of heat exchangers.

It’s a non-trivial amount of space, but we’ve found this arrangement
to be highly effective. Keeping our process loop closed allows us to keep the working
fluid within helium compressor specifications (no algae!) while reducing the amount
and complexity of equipment we need to maintain.

Best,
Alex

Alex Paterson
The National Magnetic Resonance Facility at Madison (NMRFAM)
University of Wisconsin-Madison
alpaterson_at_wisc.edu

> From: main_at_ammrl.groups.io On Behalf Of Fulton, Luke via groups.io
> Sent: Tuesday, July 29, 2025 11:27 AM
> To: main_at_ammrl.groups.io
> Subject: [AMMRL] Coolant for He Compressors

Hi all,

I'm planning end-of-life transition for our chilled water recirculator which
services two helium compressor cold heads. The main unit sits in a hallway
just outside the lab, and the building's design doesn't allow for putting
it anywhere else.

1) Any recommendations for vendor or chiller type? I'm also interested in
general quotes (feel free to message me privately with any insights on what
we might expect).

2) Some in my department are pushing for integrating into the chemistry building's
existing chilled water network. I've not heard of labs choosing this approach,
and my impression is endless complications from algae and othersundry building
issues. Anyone seen success with this? Or is it one of those 39-and-a-half-foot-pole topics?

Kind regards,
Luke

Luke Fulton, PhD
CHEM BLDG R003
NMR Core Facility Director
Unit 3060
COR2E & Department of Chemistry
55 N Eagleville Road
University of Connecticut
Storrs, CT 06279
email: fko24003_at_uconn.edu<mailto:fko24003_at_uconn.edu>
(alias): luke.fulton_at_uconn.edu<mailto:luke.fulton_at_uconn.edu>



-=-=-=-=-=-=-=-=-=-=-=-
Groups.io Links: You receive all messages sent to this group.
View/Reply Online (#2595): https://urldefense.com/v3/__https://ammrl.groups=
.io/g/main/message/2595__;!!PvDODwlR4mBZyAb0!QwGB-jJJRtlBld1uyF_P-OKqg_AA_q=
LcKmiXNUTSq9yU3GW6Q7pht5ZgAt5bNPeqF4hKkNsm5OAL5XZBjgKMeb4fx-Yo$
Mute This Topic: https://urldefense.com/v3/__https://groups.io/mt/114434070=
/7559972__;!!PvDODwlR4mBZyAb0!QwGB-jJJRtlBld1uyF_P-OKqg_AA_qLcKmiXNUTSq9yU3=
GW6Q7pht5ZgAt5bNPeqF4hKkNsm5OAL5XZBjgKMeeQzPNY7$
Group Owner: main+owner_at_ammrl.groups.io
-=-=-=-=-=-=-=-=-=-=-=-




Received on Tue Jul 29 2025 - 11:52:41 MST

This archive was generated by hypermail 2.4.0 : Sat Aug 02 2025 - 14:13:11 MST